- Amperage Rating: 210 A
- Coil Voltage: 100 to 250 VAC
- Dimensions: 270 mm L x 360 mm W x 420 mm H
- Enclosure Type: NEMA 1/4X/12/IP10/IP20/IP66
- Frequency Rating: 50/60 Hz
- Full Load Current: 192 A
- Motor Power: 110/132/184 kW
- Operating Temperature: -13 to 140 deg F
- Overload Relay: Class 10
- Phase: 3
- Series: PST
- Timing: 1 to 30 s Start, 0 to 30 s Stop
- Type: Advanced Range
- Voltage Rating: 208 to 690 VAC
- Connection type: In-Line Screw
ABB Soft Starter, Advanced Range, Series: PST, 208 to 690 VAC, 210 A, 50/60 Hz Frequency, 110/132/184 kW Motor, 100 to 250 VAC Coil, 1 to 30 s Start, 0 to 30 s Stop Timing, 3 ph, In-Line Screw Connection, Class 10 Overload Relay, 192 A Full Load, NEMA 1/4X/12/IP10/IP20/IP66 Enclosure, -13 to 140 deg F Operating, 270 mm L x 360 mm W x 420 mm H Dimensions
- Item Features
- Both in-line and inside delta connection
- Coated circuit boards available for reliable operation even in harsh environments
- Full text display in 14 languages and 4-button keypad for easy set-up and operation
- Built-in by-pass contactor on PSTB (from 370 A) for energy saving and easy installation
- Prepared for external by-pass on PST (30 to 300 A)
- Torque control for excellent control of pumps
- Fieldbus communication using Profibus, Modbus, Devicenet or CANopen
- Dual motor overload protection with classes 10A, 10, 20 and 30
- Adaptable motor underload protection to detect pumps running dry
- Adaptable locked rotor protection to detect jammed pumps
- PTC protection to protect the motor from overheating
- Adjustable kick start to start jammed pumps
- Programmable output signal relays
- Programmable pre-warning functions
- Event log with time stamp
- Analog output showing current, voltage, power factor 0 to 10 V, 0 to 20 mA, 4 to 20 mA
- 110 kW at 400 V, 132 kW at 500 V, 184 kW at 690 V 3 ph motor power rating