WAGO 750-403 Programmable Logic Controller Distributed On Machine I/O Subsystem
931457
MFG #: 750-403
$56.29
/ EA
Usually Ships within 5-8 Days
- Color: Light gray
- Conformity marking: CE
- Connection technology: 8 x CAGE CLAMP®
- Connection type (1): Inputs/outputs
- Country of origin: DE
- Current carrying capacity (power jumper contacts): 0.416666666666667
- Customs tariff number: 85389099990
- Depth: 69.8 mm / 2.748 inch
- Depth from upper edge of DIN-rail: 62.6 mm / 2.465 inch
- EMC emission of interference: Per EN 61000-6-4, marine applications
- EMC immunity to interference: Per EN 61000-6-2, marine applications
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Fire load: 1.161 MJ
- GTIN: 4045454424732
- Height: 100 mm / 3.937 inch
- Housing material: Polycarbonate, polyamide 6.6
- Indicators: LED (A-D) green: Status DI 1 … DI 4
- Input characteristic: High-side switching
- Input current per channel for signal (1) (typ.): 4.5 mA
- Input data width (internal) (max.): 4 bit
- Input filter (digital): 0.2 ms
- Isolation: 500 V system/field
- Mounting position: Horizontal (standing/lying); vertical
- Mounting type: DIN-35 rail
- Number of digital inputs: 4
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
- Operating altitude: 0 … 2000 m
- Packaging type: BOX
- Permissible H2S contaminant concentration at a relative humidity 75 %: 10 ppm
- Permissible SO2 contaminant concentration at a relative humidity 75 %: 25 ppm
- Pollution degree (5): 2 per IEC 61131-2
- Power consumption (5 V system supply): 7.5 mA
- Protection type: IP20
- Relative humidity (without condensation): 0.95
- Sensor connection: 2 x (2-wire, 3-wire); A suitable field side connection module (e.g., 750-614) must also be used to connect other sensors.
- Shock resistance: 15g per IEC 60068-2-27
- Signal type: Voltage
- Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Strip length: 8 … 9 mm / 0.31 … 0.35 inch
- Supply voltage (field): DC 24 V (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Supply voltage (sensor): DC 24 V
- Supply voltage (system): DC 5 V; via data contacts
- Surrounding air temperature (operation): 0 … 55 °C
- Surrounding air temperature (storage): -40 … 85 °C
- Total number of channels (module): 4
- Vibration resistance: 4g per IEC 60068-2-6
- Voltage range for signal (0): −3 … +5 VDC
- Voltage range for signal (1): 15 … 30 VDC
- Voltage signal type: DC 24 V
- Weight: 46.949 g
- Width: 12 mm / 0.472 inch
4-channel digital input; 24 VDC; 0.2 ms; light gray