WAGO 750-494/000-001 Programmable Logic Controller Distributed On Machine I/O Subsystem

2318289 MFG #: 750-494/000-001
$452.88 / EA
Usually Ships within 5-8 Days
  • Calculated values: Line-to-line voltage, power output, energy, power factors, mains frequency, harmonic analysis (up to the 41st harmonic), THD
  • Color: Light gray
  • Conformity marking: CE
  • Connection technology: 8 x CAGE CLAMP®
  • Connection type (1): Inputs/outputs
  • Country of origin: DE
  • Current path input resistance (typ.): 5 mΩ
  • Customs tariff number: 85389099990
  • Data width: 2 x 128-bit data; 2 x 64-bit control/status
  • Depth: 67.8 mm / 2.669 inch
  • Depth from upper edge of DIN-rail: 60.6 mm / 2.386 inch
  • EMC emission of interference: Per EN 61000-6-3
  • EMC immunity to interference: Per EN 61000-6-2
  • Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
  • Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Fire load: 0.000 MJ
  • Frequency range (harmonics analysis): 0 … 3300 Hz
  • Frequency range (mains frequency): 45 … 65 Hz
  • GTIN: 4050821548249
  • Height: 100 mm / 3.937 inch
  • Housing material: Polycarbonate, polyamide 6.6
  • Isolation: 4 kV system/field
  • Limit frequency: 15.9 kHz
  • Measurement components: Evaluating
  • Measurement current (max.): 0.208333333333333
  • Measurement cycle time: Adjustable for arithmetic mean value, min./max. values
  • Measurement error – deviation (max.) from the upper-range value: 0.005
  • Measurement error (reference temperature): 25 °C
  • Measurement method: True RMS measurement
  • Mounting position: Horizontal (standing/lying); vertical
  • Mounting type: DIN-35 rail
  • Number of measurement inputs: 6 (3 voltage measurement inputs, 3 current measurement inputs)
  • Operating altitude: 0 … 2000 m
  • Packaging type: BOX
  • Permissible H2S contaminant concentration at a relative humidity 75 %: 10 ppm
  • Permissible SO2 contaminant concentration at a relative humidity 75 %: 25 ppm
  • Pollution degree (5): 2
  • Power consumption (5 V system supply): 100 mA
  • Protection type: IP20
  • Rated surge voltage: 4 kV
  • Rated voltage: ULN = 277 V AC/DC; ULL = 480 VAC
  • Reference for measurement error: AC current/voltage
  • Relative humidity (without condensation): 0.95
  • Resolution [bit]: 24 bit
  • Shock resistance: 15g per IEC 60068-2-27
  • Signal form: Any periodic signals (considering the threshold frequencies)
  • Signal type: Power measurement
  • Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Strip length: 8 … 9 mm / 0.31 … 0.35 inch
  • Supply voltage (system): DC 5 V; via data contacts
  • Surrounding air temperature (operation): 0 … 55 °C
  • Surrounding air temperature (storage): -40 … 85 °C
  • Vibration resistance: 4g per IEC 60068-2-6
  • Voltage path input resistance (typ.): 1072 kΩ
  • Weight: 48.500 g
  • Width: 12 mm / 0.472 inch

3-Phase Power Measurement; 480 VAC, 5 A; light gray