WAGO 857-424 Programmable Logic Controller Distributed On Machine I/O Subsystem

2342961 MFG #: 857-424
$395.45 / EA
Usually Ships within 5-8 Days
  • Cable type: Shielded cable
  • Configuration options: DIP switch
  • Conformity marking: CE
  • Connection technology: Push-in CAGE CLAMP®
  • Country of origin: DE
  • Customs tariff number: 85437090300
  • Depth: 94 mm / 3.701 inch
  • EMC emission of interference: EN 61000-6-3; EN 61326-1; EN 50121-3-2
  • EMC immunity to interference: EN 61000-6-2; EN 61326-1; EN 50121-3-2
  • Fine-stranded conductor: 0.34 … 2.5 mm² / 22 … 14 AWG
  • Fire load: 0.000 MJ
  • GTIN: 4055143595476
  • Height from upper-edge of DIN-rail: 97.8 mm / 3.85 inch
  • Input current (max.): 50 mA
  • Input resistance (current input): ≤ 50 Ω
  • Input resistance (voltage input): ≥ 100 kΩ
  • Input signal (current): 0 … 10 mA; 2 … 10 mA; 0 … 20 mA; 4 … 20 mA
  • Input signal (voltage): 0 … 5 V; 1 … 5 V; 0 … 10 V; 2 … 10 V
  • Input signal type: Voltage || Current
  • Input voltage (max.): 30 V
  • Insulation type (input/analog output 1/analog output 2/supply): Reinforced insulation
  • Limit frequency: 100 Hz / 1 kHz (configurable via DIP switch)
  • Line-to-neutral conductor voltage (AC) max.: 300 V
  • Load impedance (current output): ≤ 600 Ω (per channel)
  • Load impedance (voltage output): ≥ 2 kΩ (per channel)
  • Mounting type: DIN-35 rail
  • Nominal supply voltage US: DC 24 V
  • Operating altitude (max.): 2000 m
  • Output signal (current): 0 … 10 mA; 2 … 10 mA; 0 … 20 mA; 4 … 20 mA (calibrated switching)
  • Output signal (voltage): 0 … 10 V; 2 … 10 V
  • Output signal type: Voltage || Current
  • Overvoltage category: II
  • Packaging type: Bag
  • Pollution degree: 2
  • Power consumption at nominal supply voltage: ≤ 35 mA (typ.; ≤ 250 mA max.)
  • Power supply type: 24 VDC
  • Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Standards/Specifications: EN 61010-1; EN 61373
  • Step response (typ.): 3.5 ms (100 Hz); 300 µs (1 kHz)
  • Strip length: 9 … 10 mm / 0.35 … 0.39 inch
  • Supply voltage range: -60 … +30 %
  • Surrounding air temperature (operation): -40 … 70 °C (for single module; -40 … +60 °C for module assembly)
  • Surrounding air temperature (storage): -40 … 85 °C
  • Temperaturbereich der Anschlussleitung gemäß UL 61010-2-201 min.: 90 °C
  • Temperature coefficient: ≤ 0.01 %/K
  • Temperature range of the connecting cable according to EN 61010-2-201: ≥ (Tsurrounding air + 10 K)
  • Test voltage (input/analog output 1/analog output 2/supply): 3 kVAC; 50 … 60 Hz; 1 min
  • Transmission error (typ.): ≤ 0.1 % of upper-range value
  • Weight: 41.514 g
  • Width: 6 mm / 0.236 inch

Isolation amplifier; Current and voltage input signal; Supply voltage: 24 VDC; 6 mm module width