Image Disclaimers Message
Appleton EYAX200 Conduit Sealing Fitting
Part Number # EYAX200
SKU # 2262512
Appleton EYAX200 Key Features
Appleton EYAX200 Conduit Sealing Fitting
Brand: Appleton
Part Number: EYAX200
O-Z/Gedney Conduit Sealing Fitting, Vertical/Horizontal Female, 2 in, For Use With: Threaded RMC and IMC Conduit, Ductile/Malleable Iron, Electro-Zinc Plated/Polished Chrome/Epoxy Powder Coated, 7-1/2 in L x 3-1/2 in W
Additional Description: APLE-EYAX200 2 IN HOR/VERT SEALING FTG
Catalog Description: Explosionproof Conduit Sealing Fitting, Turning Radius 2-5/8 Inch, Trade Size 2 Inch, Connection Type Female, Female, Material Zinc Electroplated Chromate Epoxy Powder Coated Ductile/Malleable Iron, Mounting Position Horizontal/Vertical, Enclosure Class I Div 1 and 2 Group C D, Class I Zone 1 and 2 Group IIA IIB, Class II Div 1 and 2 Group E F G, Class III, Approval UL 886, CSA C22.2, Overall Length 7-1/2 Inch, Application Seal Conduits in Vertical or Horizontal, to Minimize the Passage of Gases and Vapors and Prevent the Passage of Flames from One Portion of the Electrical System to Another Through the Conduit, Constructional Feature Explosionproof
EYAX200 Application
Seal conduits in vertical or horizontal, to minimize the passage of gases and vapors and prevent the passage of flames from one portion of the electrical system to another through the conduitEYAX200 Item Features
- Explosionproof, dust-ignition proof, raintight
- Prevent passage of gases, vapors or flames from one portion of conduit system to another
- Restrict any explosion to the sealed off enclosure
- Prevent pressure piling within conduit system
- Required in class I, division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
- Required in class I, division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
- Required in class I, division 1 and 2 locations at the boundary where conduit leaves classified location
- Required in class I, division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
- Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, division 2 locations
- Smooth, rounded integral bushing in each hub protects conductor insulation
- Accurately tapped, tapered threads for tight, rigid joints and ground continuity
- Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
- UL Listed for use with Kwiko A Sealing Compound, also listed with certain competitors sealing cement, contact factory for details
- Allow up to 40% conduit fill in compliance with the national electrical code
EYAX200 Standards
CEC Class I Division 1 and 2 Groups C D, Class I Zone 1 and 2 Groups IIA, IIB, Class II Division 1 and 2 Groups E, F, G, Class III|CSA 009795/C22.2 No. 30|NEC 500/503/505|Military Specification Mil-F-28675|UL 886/E-10444/E-34997SKU #2262512Part Number #EYAX200UNSPSC39121311UPC00783126113990