Image Disclaimers Message
Schneider Electric LC1D40AM7 Tesys D Everlink Iec Contactor
Part Number # LC1D40AM7
SKU # 2186393
Schneider Electric LC1D40AM7 Key Features
Schneider Electric LC1D40AM7 Tesys D Everlink Iec Contactor
Brand: Schneider Electric
Part Number: LC1D40AM7
Schneider Electric TeSys D EverLink IEC Contactor, LC1D D-Line, 220 VAC Coil, 60 A Maximum Load Current, 30 hp Coil, 3 Pole, 50/60 Hz Frequency, 5.4/2.4 kW Wattage, 3NO Contact Configuration, 1NO-1NC Auxiliary Contacts, 40 A at 440 VAC Contact, Screw Clamp Connection, Screw Clamp Terminal, Open Enclosure, 6000000 Cycles Operating Cycles, -23 to 140 deg F Operating, Surface Mounting, 2.17 in W x 4.72 in D x 4.8 in H Dimensions
Additional Description: SQD -LC1D40AM7 TeSys 3P EVLK CTR 40A 18,5KW AC3 220VAC 40A IEC AC3 40A IEC
Catalog Description: IEC contactor, TeSys Deca, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 220VAC 50/60Hz coil, open
LC1D40AM7 Application
For motor control and resistive loadsLC1D40AM7 Item Features
- Conforming to IEC 60947 rated impulse withstand voltage
- III overvoltage category
- 60 A at 140 deg F power circuit, 10 A at 140 deg F signaling circuit conventional free air thermal current
- 800 A at 440 VAC power circuit conforming to IEC 60947/140 A AC signaling circuit conforming to IEC 60947-5 1/250 A DC signaling circuit conforming to IEC 60947-5 1 IRMS rated making capacity
- 800 A at 440 VAC power circuit conforming to IEC 60947 rated breaking capacity
- 80 A gG at 690 VAC coordination type 2-power circuit/80 A gG at 690 VAC coordination type 1 power circuit/10 A gG signaling circuit conforming to IEC 60947-5-1 associated fuse rating
- 1.5 MOhm at 50 Hz, 60 A power circuit average impedance
- 12 to 26 ms closing/4 to 19 ms opening operating time
- 3600 cycles/hr at 140 deg F operating rate
- Without built-in suppressor module coil technology
- 4 to 5 W heat dissipation
- 140 VA at 68 deg F 60 Hz, 160 VA at 68 deg F 50 Hz inrush power
- 13 VA at 68 deg F 60 Hz, 15 VA at 68 deg F 50 Hz hold-in power consumption
- 25 to 400 Hz signaling circuit frequency
- 5 mA minimum switching current
- 17 VAC signaling circuit minimum switching voltage
- 1.5 ms on energization between NC and NO contacts/1.5 ms on de-energization between NC and NO contacts non-overlap time
- >10 MOhm signaling circuit insulation resistance
- TH protective treatment
- 3 degree of pollution
- https://www.youtube.com/embed/kW01lFljKgE
LC1D40AM7 Standards
RoHS Compliant|CSA C22.2 #14 File #LR43364 Class 3211 04|EN/IEC 60647-4/60947-5-1|UL File #E164862 NLDX/508|CCC/CE Certified|DNV Approved|BV/GL/LROS/DINA Certified|ECCN EAR99|PROP65: This product can expose you to chemicals including: Antimony oxide and Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65warnings.ca.govSKU #2186393Part Number #LC1D40AM7UNSPSC39121529UPC00785901734901