Image Disclaimers Message
Schneider Electric LC1D50AM7 Everlink Tesys D Iec Contactor
Part Number # LC1D50AM7
SKU # 2182105
Schneider Electric LC1D50AM7 Key Features
Schneider Electric LC1D50AM7 Everlink Tesys D Iec Contactor
Brand: Schneider Electric
Part Number: LC1D50AM7
Schneider Electric EverLink Square D TeSys D IEC Contactor, Direct On-Line, Series: LC1D, 220/690 VAC, 300 VDC Coil, 50/80 A Maximum Load Current, 13/16 VA Coil, 3 Pole, 50/60 Hz Frequency, 9.6/3.7 W Wattage, 3NO Contact Configuration, 1NO-1NC Auxiliary Contacts, 10/60 A at 440 VAC, 60 to 80 A at 440 VAC Contact, Screw Clamp Connection, 120/122/55 mm Size, Screw Clamp Terminal, Open Enclosure, 3600 cycles/hr Operating Cycles, -5 to 60/-40 to 70 deg C Operating, Rail/Surface Mounting, 55 mm W x 1
Additional Description: SQD -LC1D50AM7 TeSys 3P EVLK CTR 50A 22KW AC3 220VAC 50A IEC
Catalog Description: IEC contactor, TeSys Deca, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 220VAC 50/60Hz coil, open
LC1D50AM7 Application
For motor control and resistive loadsLC1D50AM7 Item Features
- Conforming to IEC 60947 rated impulse withstand voltage
- III overvoltage category
- 80 A at 140 deg F power circuit, 10 A at 140 deg F signaling circuit conventional-free air thermal current
- 900 A at 440 VAC power circuit conforming to IEC 60947/140 A AC signaling circuit conforming to IEC 60947-5 1/250 A DC signaling circuit conforming to IEC 60947-5 1 IRMs rated making capacity
- 900 A at 440 VAC power circuit conforming to IEC 60947 rated breaking capacity
- 100 A gG at 690 V coordination type 2 power circuit/100 A gG at 690 V coordination type 1 power circuit/10 A gG signaling circuit conforming to IEC 60947-5-1 associated fuse rating
- 1.5 MOhm at 50 Hz, 60 A power circuit average impedance
- 12 to 26 ms closing/4 to 19 ms opening operating time
- 3600 cycles/hr at 140 deg F operating rate
- Without built-in suppressor module coil technology
- 4 to 5 W heat dissipation
- 140 VA at 68 deg F 60 Hz, 160 VA at 68 deg F 50 Hz inrush power
- 13 VA at 68 deg F 60 Hz, 15 VA at 68 deg F 50 Hz hold-in power consumption
- 25 to 400 Hz signaling circuit frequency
- 5 mA minimum switching current
- 17 VAC signaling circuit minimum switching voltage
- 1.5 ms on energization between NC and NO contact/1.5 ms on de-energization between NC and NO contact non-overlap time
- >10 MOhm signaling circuit insulation-resistance
- TH protective treatment
- 3 deg of pollution
- https://www.youtube.com/embed/ZspiS_-OK5U
LC1D50AM7 Standards
BV/GL/LROS/DINA Certified|CCC Certified|CE Certified|CSA C22.2 File No. 14 File No. LR43364 Class 3211 04|DNV Approved|ECCN EAR99|EN/IEC 60647-4/60947-5-1|PROP65: This product can expose you to chemicals including: Antimony oxide and Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65warnings.ca.gov|RINA|RoHS Compliant|UL File No. E164862 NLDX/508SKU #2182105Part Number #LC1D50AM7UNSPSC39121529UPC00785901565246