Siemens 3UB81134BB2 Key Features
| Brand: | Siemens |
|---|---|
| Part Number # : | 3UB81134BB2 |
| SKU #: | 2194158 |
| Amperage Rating: | 0.75 to 3.4, 0.75 to 3.4 A |
| Contact Form: | 1NC-1NO, 1NO-1NC, 1NO-1NC 1 Form A/1 Form B |
| Contact Rating: | 3.4 A at 600 VAC |
| Dimensions: | 2.12 in H, 4.61 in L x 4.38 in W x 3.98 in H |
| Number of Poles: | 3 |
| Series: | ESP200 |
| Temperature Rating (Degrees F): | -25 to 60, -25 to 65 deg C |
| Terminal Type: | Screw, Threaded |
| Type: | 3-Phase Solid State |
| Country of origin: | CZ |
| Mounting type: | DIN Rail, Direct/Stand Alone |
| Manufacturer Name: | Siemens |
| UNSPSC: | 39122330 |
| UPC: | 00662643897197 |
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
Siemens 3UB81134BB2 Overload Relay
Brand: Siemens
Part Number: 3UB81134BB2
Siemens Overload Relay, 3-Phase Solid State, Series: ESP200, 0.75 to 3.4 A, 1NC-1NO Contact Form, Direct/Stand Alone Mounting, Screw Terminal, -25 to 65 deg C, 2.12 in H Dimensions
Additional Description: SIEM-3UB81134BB2 OVERLOAD RELAY,0.75-3.4AMPS,3PH,ESP200 ESP200
Catalog Description: Esp200 catalog no 48atb3s00 solid state overload relay for motor protection 0.75 to 3.4 amp size a 3 phase class 5...30, switchable direct mounting and stand-alone main circuit screw terminals auxiliary circuit scrw terminal manual automatic reset
3UB81134BB2 Application
For motor protection applications3UB81134BB2 Item Features
- Trip classes- 5, 10, 20 or 30 selectable by DIP switches field changeable reduces time and inventory suitable for light, normal and heavy starting conditions
- Phase loss protection trips in less than 3 sec protects motor burn out and minimizes motor heating up
- Phase unbalance trips based on trip class selected minimizes temperature rise of the motor on a asymmetrical 3-phase system
- Ground fault trips 60% of motor current provides optimum system protection of motors against high resistance short circuits or ground faults due to moisture, condensation, damage of insulation or any other reason
- Trip indicator visible-save time, faster to identify overload trip
- Ambient insensitive-prevents nuisance tripping
- No heaters required-saves cost and eliminates time for installation of heaters
- Self-powered no outside source required-reduce cost for external power supply
- FLA dial with wide adjustment 4:1 ratio provides wide range, reduces inventory
- Self-protected in short circuit condition (when used with proper fuses or motor starter protector-unlike bimetal overloads, this eliminates replacement of the overload heaters after short circuit
- Test button tests electronics tests the complete electronic functions including the trip mechanism increases up time
- Thermal memory prevents re-starting motor when it is still hot
- Conformally coated circuit board resists against environmental conditions
- 1NO-1NC contacts standard B600, R300 makes it easier for user to wire local contacts
- Wide operating temperature range prevents nuisance tripping with temperature changes
- Repeat accuracy <1% for more precise settings and reduced nuisance tripping
- Removable terminal block terminal block can be removed without removing wires saves time for replacements
- Automatic reset is 3 min after tripping, allowing motor to cool down before re-start, if manual reset is selected, overload can be reset immediately
- Remote reset as an alternative to the mechanical reset options, an electrical remote reset can be used by applying 24 VDC to terminals A3 and A4
- Touch safe terminal protects against accidental touching of live circuits
3UB81134BB2 Standards