Part Number # LC2K0601F7
SKU # 2224696
Image Disclaimers Message
Square D LC2K0601F7 Key Features
| Brand: | Square D |
|---|---|
| Part Number # : | LC2K0601F7 |
| SKU #: | 2224696 |
| Coil Power Rating: | 3, 3 kW |
| Coil Voltage: | 110, 110 VAC |
| Contact Configuration: | 3NO |
| Contact Rating: | 6 A at 440 VAC, 6 A at 575 VAC |
| Dimensions: | 2.28 in H x 3.54 in W x 2.24 in D, 3.54 in W x 2.24 in D x 2.28 in H |
| Enclosure Type: | IP20 |
| Frequency Rating: | 50/60, 50/60 Hz |
| Number of Auxiliary Contacts: | 1NC |
| Number of Poles: | 3 |
| Operating Cycles: | 5000000, 5000000 Cycles |
| Operating Temperature: | -13 to 122, -13 to 122 deg F |
| Series: | LC2K |
| Terminal Type: | Screw Clamp, Screw/Clamp |
| Type: | K-Line LC2K, Reversing |
| Country of origin: | FR |
| Mounting type: | Plate/Rail, Surface |
| Manufacturer Name: | Schneider Electric |
| UNSPSC: | 39121529 |
| UPC: | 00785901882848 |
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
$129.10 / Each
Quantity:
Square D LC2K0601F7
Brand: Square D
Part Number: LC2K0601F7
Additional Description: SQD -LC2K0601F7 REVERSING CONTACTOR
Catalog Description: Reversing contactor, TeSys K, 3P, AC-3, lt or eq to 440V 6A, 1 NC, 110VAC coil
LC2K0601F7 Application
For resistive and motor controlLC2K0601F7 Item Features
- 8 kV rated impulse withstand voltage
- III overvoltage category
- 20 A at <=122 deg F (50 deg C) power circuit/10 A at <=122 deg F (50 deg C) signaling circuit conventional free air thermal current
- 25 A gG at <=440 V power circuit/25 A aM power circuit/10 A gG signaling circuit conforming to IEC 60947/10 A gG signaling circuit conforming to VDE 0660 associated fuse rating
- 3 mOhm at 50 Hz - Ith 20 A power circuit average impedance
- Mechanical interlock
- 1.3 Nm on screw clamp terminals with screwdriver Philips No 2/flat 6 mm diameter tightening torque
- 10 to 20 ms coil de-energisation and NO opening/coil energisation and NO closing operating time
- 3600 cycles/hr operating rate
- 30 VA at 68 deg F (20 deg C) inrush power
- 4.5 VA at 68 deg F (20 deg C) hold-in power consumption
- 1.3 W heat dissipation
- <=400 Hz signaling circuit frequency
- 5 mA signaling circuit minimum switching current
- 17 V signaling circuit minimum switching voltage
- 0.02 in (0.5 mm) non-overlap distance
- >10 MOhm signaling circuit insulation resistance
- TC protective treatment
- 6561.68 ft (2000 m) without derating in temperature operating altitude
- 3 kW at 440 VAC 50/60 Hz, 3 kW at 500 to 600 VAC 50/60 Hz, 3 kW at 660 to 690 VAC 50/60 Hz, 1.5 kW at 220 to 230 VAC 50/60 Hz
LC2K0601F7 Standards
UL Listed|IEC 60947|BS 5424|VDE 0660|NF C 63-110|CSA CertifiedSKU #2224696Part Number #LC2K0601F7UNSPSC39121529UPC00785901882848