Part Number # APPEYM75
SKU # 2214414
Image Disclaimers Message
APPEYM75
Appleton APPEYM75 Conduit Sealing Fitting
Part Number # APPEYM75
SKU # 2214414
Appleton APPEYM75 Key Features
| Brand: | Appleton | 
|---|---|
| Part Number # : | APPEYM75 | 
| SKU #: | 2214414 | 
| Dimensions: | 4.71 in L x 1.38 in W | 
| Finish: | Triple Coated | 
| Series: | EY Series | 
| Size: | 3/4, 3/4 in | 
| Suitable For Use With: | IMC/Threaded Rigid Metallic Conduit | 
| Type: | Dust-Ignitionproof Explosionproof Raintight | 
| Country of origin: | MX | 
| Material: | Malleable Iron | 
| Manufacturer Name: | Emerson Electric | 
| UNSPSC: | 39121311 | 
| UPC: | 00781381135375 | 
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
- Appleton APPEYM75 Conduit Sealing Fitting - Brand: Appleton - Part Number: APPEYM75 - Appleton UNILETS Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 3/4 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple Coated, 4.71 in L x 1.38 in W - Additional Description: APLE-APPEYM75 3/4 EXP PROOF SEAL. UNILET - Catalog Description: UNILETS EY Series 25 PCT Fill Vertical And Horizontal Conduit Sealing Fitting With Removable Nipple, Size: 3/4 IN, Material: Malleable Iron, Finish: Triple-Coat (Zinc Electroplate, Chromate And Epoxy Powder Coat), Connection: Female Threade - APPEYM75 ApplicationFor prevent passage of gases, vapors or flames from one portion of conduit system to another- APPEYM75 IncludesRemovable Male Nipple- APPEYM75 Item Features- Smooth, rounded integral bushing in each hub to protect conductor insulation
- Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
- Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
- Restrict any explosion to the sealed off enclosure
- Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
- Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
- Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
- Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
- Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
- 25% fill vertical and horizontal conduit sealing fittings for close turning radius
- Chromate/epoxy powder coated/zinc electroplated finish
 - APPEYM75 StandardsUL 886|UL 1203|UL File No. E10444|CSA C22.2 No. 30|CSA 065181, Class I, Groups A, B, C, D, Class II, Groups E, F, G, Class III- APPEYM75 WarrantyLimitedSKU #2214414Part Number #APPEYM75UNSPSC39121311UPC00781381135375