EYDM100AL
Appleton EYDM100AL
Part Number # EYDM100AL
SKU # 2469805
Appleton EYDM100AL Key Features
| Brand: | Appleton |
|---|---|
| Part Number # : | EYDM100AL |
| SKU #: | 2469805 |
| Dimensions: | 4.06 in L x 1.56 in W |
| Series: | EYDM |
| UNSPSC: | 39121311 |
| UPC: | 00781381619844 |
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
Appleton EYDM100AL
Brand: Appleton
Part Number: EYDM100AL
Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EYDM, 1 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated, 4.06 in L x 1.56 in W
Additional Description: APLE-EYDM100AL DRAIN SEALING FITTING ALMAG 35
Catalog Description: UNILETS EYDM Series 25 PCT Fill Vertical Conduit Drain Sealing Fitting With Removable Nipple, Size: 1 IN, Material: Almag 35 Aluminum, Finish: Epoxy Powder Coat, Connection: Tapered MNPT X Tapered FNPT, Turning Radius: 2.06 IN, Length: 4.06 IN, Width: 1.56 IN, Standard: UL 886 (1203), UL File Number E10444, CSA C22.2 No. 30, CSA 065181, UL Listed For Class I, Groups B, C, D, Class II, Groups E, F, G, And Class III, For Use With Threaded Rigid Metal Conduit and IMC
EYDM100AL Application
For prevent passage of gases, vapors or flames from one portion of conduit system to anotherEYDM100AL Item Features
- Smooth, rounded integral bushing in each hub to protect conductor insulation
- Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
- Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
- Close radius type for sealing vertical conduit runs
- Restrict any explosion to the sealed off enclosure
- Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
- Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
- Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
- Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
- Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
- Tapered MNPT X tapered FNPT connection
- 25% fill vertical conduit drain sealing fittings
- Access cover has drain valve for automatic draining of water accumulation above the seal
EYDM100AL Standards
UL 886|UL 1203 File No. E10444|CSA C22.2 No. 30|CSA 065181SKU #2469805Part Number #EYDM100ALUNSPSC39121311UPC00781381619844