EYSF300
Appleton EYSF300
Part Number # EYSF300
SKU # 2469883
Appleton EYSF300 Key Features
| Brand: | Appleton |
|---|---|
| Part Number # : | EYSF300 |
| SKU #: | 2469883 |
| Dimensions: | 8.5 in L x 4.13 in W |
| UNSPSC: | 39121311 |
| UPC: | 00781381331159 |
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
Appleton EYSF300
Brand: Appleton
Part Number: EYSF300
Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EYS, 3 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple Coated, 8.5 in L x 4.13 in W
Additional Description: APLE-EYSF300 SEALING FIT'G EXP-PROOF 3
Catalog Description: UNILETS EYS Series 25 PCT Fill Vertical Conduit Sealing Fitting, Size: 3 IN, Material: Malleable Iron, Finish: Triple-Coat (Zinc Electroplate, Chromate And Epoxy Powder Coat), Connection: Tapered FNPT, Turning Radius: 5.63 IN, Length: 8-1/2 IN, Width: 4.13 IN, Standard: UL 886 (1203), UL File Number E10444, CSA C22.2 No. 30, CSA 065181, For Use With Threaded Rigid Metal Conduit and IMC
EYSF300 Application
For prevent passage of gases, vapors or flames from one portion of conduit system to anotherEYSF300 Item Features
- Smooth, rounded integral bushing in each hub to protect conductor insulation
- Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
- Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
- Large opening for damming and filling
- Restrict any explosion to the sealed off enclosure
- Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
- Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
- Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
- Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
- Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
- Tapered FNPT connection
- 25% fill vertical conduit sealing fittings
- Chromate/epoxy powder coated/zinc electroplated finish
EYSF300 Standards
UL 1203 File No. E10444|CSA C22.2 No. 30|CSA 065181SKU #2469883Part Number #EYSF300UNSPSC39121311UPC00781381331159
Image provided may only be a representation of final product and may include optional equipment