Part Number # LPS-RK-40SP
SKU # 8225
Image Disclaimers Message
LPS-RK-40SP
Bussmann LPS-RK-40SP Time Delay Fuse
Part Number # LPS-RK-40SP
SKU # 8225
$840.40 / 10Each
Typical price:$1235.40 / Each
Bussmann LPS-RK-40SP Key Features
| Brand: | Bussmann |
|---|---|
| Part Number # : | LPS-RK-40SP |
| SKU #: | 8225 |
| Amperage Rating: | 40, 40 A |
| Body Type: | Cylindrical |
| Class: | RK1 |
| Indicating/Non-Indicating: | Non-Indicating |
| Interrupt Rating: | 300/100, 300/100 kAIC |
| Rejection/Non-Rejection: | Rejection |
| Response Time: | 10 s at 500% |
| Series: | LPS-RK, LPS-RK-SP |
| Terminal Type: | Clip, Ferrule End |
| Type: | Current Limiting Time Delay |
| Material: | Melamine |
| Mounting type: | Holder |
| Manufacturer Name: | Eaton |
| UNSPSC: | 39121606 |
| UPC: | 00051712548380 |
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
$840.40 / 10Each
Typical price:$1235.40 / Each
Quantity:
- Bussmann Low-Peak Fuse, Current Limiting Time Delay, Series: LPS-RK, Indicating/Non-Indicating: Non-Indicating, Rejection/Non-Rejection: Rejection, 40 A, 600 V AC/300 V DC, 300/100 kAIC Interrupt, Class: RK1, 10 s at 500% Response, Ferrule End Terminal, Holder Mount, Cylindrical Body Type, Dual Element, Melamine, 1.06 in Dia x 5.5 in L Body Size
LPS-RK-40SP Application
Industrial Facilities and Factories, Safety and Security Systems, Feeder and Branch Circuits, Motors, Transformers, Solenoids and General Purpose Circuits ApplicationsLPS-RK-40SP Item Features
- Fast short circuit protection and dual element, time delay performance provide ultimate protection
- Reduces existing fuse inventory by up to 33% when upgrading to Low-Peak fuses
- Consistent 2:1 ampacity ratios for all Low-Peak fuses make selective co-ordination easy
- Time-delay permits sizing as close as 130% of motor full load amps (FLA) for back-up overload protection
- Current limitation protects downstream components against damaging thermal and magnetic effects of short circuit currents
- Protects against 1 ph motor damage
- Proper sizing can provide "no damage" type 2 motor starter protection for NEMA and the international electrotechnical commission (IEC) motor controllers
- Electrically isolated end caps for additional safety
- https://www.youtube.com/watch?v=YMvqUyoETXk
LPS-RK-40SP Standards
CE Certified|CSA C22.2 File No.53787/248.12|UL File No.E4273 Guide JDDZSKU #8225Part Number #LPS-RK-40SPUNSPSC39121606UPC00051712548380