Littelfuse MPU-32-04-00 Key Features
| Brand: | Littelfuse | 
|---|---|
| Part Number # : | MPU-32-04-00 | 
| SKU #: | 2389781 | 
| Contact Configuration: | 3CO 3 Form C, NO-NC (3 Form C) | 
| Dimensions: | 3.8 in H x 3.8 in W x 5.2 in D | 
| Display Type: | Onboard | 
| Frequency Rating: | 50/60 Hz | 
| Series: | MPU-32 | 
| Terminal Type: | Wire Clamping | 
| Country of origin: | MX | 
| Mounting type: | Panel | 
| Manufacturer Name: | Littelfuse | 
| UNSPSC: | 39122331 | 
| UPC: | 00079458978209 | 
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
$4544.11 /  Each
Typical price:$7307.78 / Each
Quantity: 
- Littelfuse Motor Protection Unit, Series: MPU-32, 65 to 265 V AC/80 to 275 V DC, 50/60 Hz Frequency, 3CO 3 Form C Contact Configuration, Panel Mounting, Wire Clamping Terminal, Onboard Display, 3.8 in H x 3.8 in W x 5.2 in D DimensionsMPU-32-04-00 ApplicationFor retrofitting and upgradingMPU-32-04-00 Item Features- Overload, extends motor life and prevents insulation failures and fires
- Dynamic thermal model provides protection through starting, running and cooling cycles
- Communications remotely view measured values and event records, reset trips and access setpoint
- Ground fault 50G/N, 51G/N prevents catastrophic failures and fires
- Current unbalance/phase loss/phase reverse prevents overheating due to unbalanced phases
- RTD temperature protection (MPS-RTD module) for high-ambient or loss-of-ventilation protection
- Phase loss/phase reverse (current) detects unhealthy supply conditions
- Overcurrent prevents catastrophic failures and fires, extends motor life
- Jam prevents motor damage by detecting mechanical jams or excessive loading
- Undercurrent detects low level or no-load conditions
- Over temperature (PTC) protection for high-ambient or loss-of-ventilation detection
- Limits the motor starts per hour to prevent overheating
- Reduced overcurrent mode minimizes arc flash hazards during maintenance
- Metering - view measured and calculated parameters with onboard display
- MPU-CIM - separate current input module to reduce risk of open-CT hazard and for convenient installation
- Analog output provides means for metering selectable parameters
- Onboard 100 event recorder for data logging
- Internal circuits are conformally coated to protect against corrosion and moisture
- RS/TIA-232, ethernet communications
 MPU-32-04-00 StandardsCSA File No. LR62897|CSA C22.2 No. 14|CE Certified|UL Recognized|C-Tick N11659SKU #2389781Part Number #MPU-32-04-00UNSPSC39122331UPC00079458978209