Littelfuse SB5060-311-0 SB5000 Series Industrial Shock Block, 600 V, 60 A
Image Disclaimers Message
Littelfuse SB5060-311-0 SB5000 Series Industrial Shock Block, 600 V, 60 A
Littelfuse SB5060-311-0 SB5000 Series Industrial Shock Block, 600 V, 60 A
Part #:SB5060-311-0
SKU #: 2410412
Key Features
Part #:SB5060-311-0
SKU #: 2410412
Brand: Littelfuse
Amperage Rating: 60 A
Dimensions: 11.25 in H x 9.56 in W x 4.44 in D
Enclosure Type: NEMA 4X/IP69K
Finish: Conformal Coating
Frequency Rating: 60 Hz
- UL 943 inverse time trip curve, Inverse time detection circuit protects people while also reducing the probability of nuisance tripping
- DFT (Discrete Fourier Transform) filtering algorithm eliminates nuisance trips due to harmonics
- Minimum trip time < 20 msec reduces the risk of ventricular fibrillation for leakage current of 250 mA and above
- Selectable trip levels(EGFPD) the settings below 20 mA provide extra safety. The settings above 20 mA can reduce nuisance tripping on systems with high leakage current
- Two-stage ground monitor with Zener termination that meets UL 943C, CSA M421
- Flexible configuration selectable manual reset or autoreset for brownout, power up, and ground monitor interruptions to fit plant safety protocols
- Auxiliary contact alerts your SCADA system if the Shock Block is energized or tripped
- Automatic self-test the Shock Block will continuously test itself and will trip if there is an internal failure
- GFCI Class A, C, D and EGFPD options in one series simplified planning and operator familiarity for multiple applications/requirements
- https://players.brightcove.net/1799386164001/default_default/index.html?videoId=6300365223001
Littelfuse SB5060-311-0 SB5000 Series Industrial Shock Block, 600 V, 60 A
Additional Description: LTFS-SB5060-311-0 SHOCK BLOCK EGFPD 600V 60A
Catalog Description: Special-Purpose Ground-Fault Circuit Interrupter (SPGFCI), Class C and Class D: Industrial Shock Block (ISB) is a personnel protection device designed to meet the requirements for special-purpose GFCIs defined by UL 943C. This standard outlines GFCI classes specifically designed for use in industrial facilities. Class C GFCIs are intended to be used on three-phase systems where the line-to-line voltage is 480 V or less with a trip level of 20 mA, while Class D GFCIs are intended to be used on 600 V systems. The Industrial Shock Block includes DFT harmonic filtering, an automatic self-test feature and is compliant to the UL 1998 Software in Programmable Components standard. Ground-Fault Circuit Interrupter (GFCI), Class A: The Shock Block is available as a 208 V Class A GFCI, allowing commercial kitchens, construction sites, and other non-dwelling units with wet areas to meet NEC 210.8(B) for their 3-phase loads up to 60 A. Equipment Ground-Fault Protective Device (EGFPD): Industrial S