Mersen A6D250R Key Features
| Brand: | Mersen | 
|---|---|
| Part Number # : | A6D250R | 
| SKU #: | 2292114 | 
| Amperage Rating: | 250, 250 A | 
| Body Type: | Cylindrical | 
| Class: | RK1 | 
| Indicating/Non-Indicating: | Indicating | 
| Interrupt Rating: | 200, 200 kA | 
| Rejection/Non-Rejection: | Rejection | 
| Series: | A6D-R | 
| Terminal Type: | Blade | 
| Type: | Current Limiting Low Voltage North American Time Delay | 
| Country of origin: | MX | 
| Material: | Fiberglass | 
| Mounting type: | Clip | 
| Manufacturer Name: | MERSEN | 
| UNSPSC: | 39121604 | 
| UPC: | 00782001992224 | 
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
$598.88 /  Each
Typical price:$1433.58 / Each
Quantity: 
- Mersen AMP-TRAP 2000 SmartSpot Power Fuse, Current Limiting Low Voltage North American Time Delay, Series: A6D-R, Indicating, Rejection, 250 A, 600 V AC, 200 kA Interrupt, Class: RK1, Blade Terminal, Clip Mounting, Cylindrical Body, Dual Element, Fiberglass, 2-9/16 in Dia x 11-5/8 in L Body
A6D250R Application
Motor, Safety Switches, Transformers, Disconnects, Control Panel and All General Purpose Circuits ApplicationsA6D250R Item Features
- Solid state SmartSpot indicator
 - Time delay for motor starting and transformer inrush currents without nuisance opening
 - 300 kA interrupting rating, self certified (UL witnessed)
 - Extremely current limiting for low peak let-thru current
 - Easy 2-to-1 selectivity for prevention of nuisance shutdowns and "blackouts"
 - Rejection style design prevents replacement errors (when used with recommended fuse blocks)
 - High visibility orange label gives instant recognition
 - Reduced inventory by taking the place of class RK5, K and H fuses
 - Metal embossed date and catalog number for easier traceability and lasting identification
 - Fiberglass body provides dimensional stability in harsh industrial settings
 - High grade silica filler ensures fast arc quenching
 - Recommended for arc flash energy reduction
 - A6D-R fuses will open fast enough under extreme fault conditions for maximum short
 - Plated terminals
 - Arc flash mitigating
 - Tin-plated copper contact
 
A6D250R Standards
CSA C22.2 No. 248.12|DC Listed|RoHS Compliant|UL 248|UL 248-12 File No. E2137SKU #2292114Part Number #A6D250RUNSPSC39121604UPC00782001992224 