- Reliable and easy operation worldwide power supply
- Resistant in tough environments
- Easy and fast installation
- Most compact class on the market
- Parallel operation
- Harmonic current emissions
- Rod terminal blocks and IP20 degree of protection
- 1.56 A boost current
- 86% efficiency
- 0.43 minimum power factor at 100% load
- 0.13 mA at 115 VAC/0.24 mA at 230 VAC leakage current
- 16 A at 115 VAC/32 A at 230 VAC at inrush current at 25 deg C cold start
- -10 to 15% voltage adjustment
- 30 mVp-p maximum at 20 MHz of bandwidth ripple and noise voltage
- 0.4% maximum input variation influence
- 0.8% maximum load variation influence
- 0.05%/deg C maximum temperature variation influence
- 600 ms at 115 VAC/480 ms at 230 VAC start up time
- 23 ms at 115 VAC/154 ms at 230 VAC hold time
- Automatic reset overload protection
Omron S8VKG03024 DC Power Supply
OMRON DC Power Supply, Covered, Series: S8VK-G, 100 to 240 VAC/90 to 350 VDC Input, 24 VDC Output, 30 W, 1.3 A, 50/60 Hz, DIN Rail Mount, 32 mm Width, 90 mm Depth, 90 mm Height
Additional Description: OMRO-S8VKG03024 SMPS,INPUT: 100 - 240 VAC,OUTPUT: 24 V S8VK-G03024
Catalog Description: Switch Mode Power Supply, Voltage Rating: Input: 100 - 240 VAC, Output: 24 V, Amperage Rating: Output: 1.3 AMP, Wattage: 30 WTT, Frequency Rating: 50/60 HZ, Phase: 1 PH, Efficiency: 0.86 Typical At 230 VAC Input, Insulation: Between All Outputs And All Inputs/ PE Terminals: 100 MOHM Minimum (At 500 VDC), Mounting: DIN Rail, Enclosure: IP20, Environmental Conditions: Ambient Operating Temperature: -40 To 70 DEG C, Storage Temperature: -40 To 85 DEG C, Ambient Operating Humidity: 0 - 95 PCT, Dielectric Strength: 3 KVAC For 1 MINT (Between All Inputs And Outputs), Vibration Resistance: 10 - 55 HZ, 0.375 MM Single Amplitude For 2 HR Each In X, Y And Z Directions, Shock Resistance: 150 M/S2, 3 Times Each In Plus/Minus X, Plus/Minus Y And Plus/Minus Z Directions, Length: 90 MM, Width: 32 MM, Height: 90 MM, Power Factor: 0.43 At 24 V, Conforms To EN61204-3 EN55011 Class B And Based On FCC Class A, Conforms To EN61204-3 EN55011 Class B, Conforms To EN61204-3 High Severity Levels, UL Listed: U