Square D LC1D128BD Tesys D Iec Contactor
Image Disclaimers Message
Square D LC1D128BD Tesys D Iec Contactor
Square D LC1D128BD Tesys D Iec Contactor
Part #:LC1D128BD
SKU #: 2141805
Key Features
Part #:LC1D128BD
SKU #: 2141805
Brand: Square D
Coil Power Rating: 5.4, 5.4 W Inrush/Hold-In
Coil Voltage: 24, 24 VDC, 690 VAC, 24/300 VDC
Contact Configuration: 2NO-2NC
Contact Rating: 25 A at 440 VAC, 25 A at 600 VAC, 25/60 A at 600 VAC, 10/60 A at 600 VAC
Dimensions: 1.77 in W x 3.9 in D x 3.35 in H, 3.35 in H x 1.77 in W x 3.9 in D, 45 mm W x 99 mm D x 85 mm H
- 25 A at <=140 deg F (60 deg C) power circuit/10 A at <=140 deg F (60 deg C) signaling circuit conventional free air thermal current
- 250 A at 440 V power circuit conforming to IEC 60947/140 A AC signaling circuit conforming to IEC 60947-5-1/250 A DC signaling circuit conforming to IEC 60947-5-1 irms rated making capacity
- 250 A at 440 V power circuit conforming to IEC 60947 rated breaking capacity
- 25 A gG at <=690 V coordination type 2 power circuit/40 A gG at <=690 V coordination type 1 power circuit/10 A gG signaling circuit conforming to IEC 60947-5-1 associated fuse rating
- 2.5 mOhm at 50 Hz - Ith 25 A power circuit average impedance
- 53.55 to 72.45 ms closing/16 to 24 ms opening operating time
- 3600 cycles/hr at <=140 deg F (60 deg C) operating rate
- With integral suppression device coil technology
- 5.4 W at 68 deg F (20 deg C) inrush power
- 5.4 W at 68 deg F (20 deg C) hold-in power consumption
- 28 ms time constant
- TH protective treatment
- 3 pollution deg
- -4 to 158 deg F permissible ambient air temperature around the device, -76 to 176 deg F storage temperature
- 9842.52 ft without derating in temperature operating altitude
- 1562 deg F (850 deg C) conforming to IEC 60695-2-1 fire resistance
- V1 conforming to UL 94 flame retardance
- Vibrations contactor open 2 gn, 5 to 300 Hz/vibrations contactor closed 4 gn, 5 to 300 Hz/shocks contactor closed 15 gn for 11 ms and shocks contactor open 6 gn for 11 ms mechanical robustness
- 25 to 400 Hz signaling circuit frequency
- 5 mA signaling circuit minimum switching current
Square D LC1D128BD Tesys D Iec Contactor
Square D TeSys D IEC Contactor, Series: LC1D, 24 VDC Coil, 25 A Maximum Load Current, 4 Pole, 50/60 Hz Frequency, 1.56 W Wattage, 2NO-2NC Contact Configuration, 1NO-1NC Auxiliary Contacts, 25 A at 440 VAC Contact, Screw Clamp Terminal, Open Enclosure, 30000000 Cycles Operating Cycles, -4 to 140 deg F Operating, Plate/Rail Mounting, 3.35 in H x 1.77 in W x 3.9 in D Dimensions
Additional Description: SQD -LC1D128BD TeSys 4P CTR 25A AC-1 2NO 2NC 24VDC COIL +OPTIONS
Catalog Description: IEC contactor, TeSys Deca, nonreversing, 25A resistive, 4 pole, 2 NO and 2 NC, 24VDC coil, open style