Part Number # LC1D128BD
SKU # 2141805
Image Disclaimers Message
Brand: Square D
LC1D128BD
Square D LC1D128BD Tesys D Iec Contactor
Part Number # LC1D128BD
SKU # 2141805
$170.52 /  Each
Square D LC1D128BD Key Features
| Brand: | Square D | 
|---|---|
| Part Number # : | LC1D128BD | 
| SKU #: | 2141805 | 
| Coil Power Rating: | 5.4, 5.4 W Inrush/Hold-In | 
| Coil Voltage: | 24, 24 V DC, 24 VDC, 690 VAC, 24/300 VDC | 
| Contact Configuration: | 2NO-2NC | 
| Contact Rating: | 25 A at 440 V AC, 25 A at 440 VAC, 25 A at 600 VAC, 25/60 A at 600 VAC, 10/60 A at 600 VAC | 
| Dimensions: | 1.77 in W x 3.9 in D x 3.35 in H, 3.35 in H x 1.77 in W x 3.9 in D, 45 mm W x 99 mm D x 85 mm H | 
| Enclosure Type: | Open | 
| Frequency Rating: | 25 to 400, 50/60, 50/60 Hz | 
| Number of Auxiliary Contacts: | 1NO-1NC | 
| Number of Poles: | 4 | 
| Operating Cycles: | 30000000, 30000000 Cycles, 3600 | 
| Operating Temperature: | -4 to 140, -4 to 140 deg F, -5 to 60/-40 to 70 | 
| Series: | LC1D | 
| Size: | 45/85/99 | 
| Terminal Type: | Screw Clamp | 
| Type: | D-Line, LC1D D-Line | 
| Wattage: | 1.56, 1.56 W | 
| Connection type: | Screw Clamp | 
| Country of origin: | ID | 
| Mounting type: | Plate/Rail, Rail/Surface, Surface | 
| Manufacturer Name: | Schneider Electric | 
| UNSPSC: | 39121529 | 
| UPC: | 00785901787495 | 
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
$170.52 /  Each
Quantity: 
- Square D TeSys D IEC Contactor, Series: LC1D, 24 VDC Coil, 25 A Maximum Load Current, 4 Pole, 50/60 Hz Frequency, 1.56 W Wattage, 2NO-2NC Contact Configuration, 1NO-1NC Auxiliary Contacts, 25 A at 440 V AC Contact, Screw Clamp Terminal, Open Enclosure, 30000000 Cycles Operating Cycles, -4 to 140 deg F Operating, Plate/Rail Mounting, 3.35 in H x 1.77 in W x 3.9 in D DimensionsLC1D128BD ApplicationFor resistive loadLC1D128BD Item Features- 25 A at <=140 deg F (60 deg C) power circuit/10 A at <=140 deg F (60 deg C) signaling circuit conventional free air thermal current
- 250 A at 440 V power circuit conforming to IEC 60947/140 A AC signaling circuit conforming to IEC 60947-5-1/250 A DC signaling circuit conforming to IEC 60947-5-1 irms rated making capacity
- 250 A at 440 V power circuit conforming to IEC 60947 rated breaking capacity
- 25 A gG at <=690 V coordination type 2 power circuit/40 A gG at <=690 V coordination type 1 power circuit/10 A gG signaling circuit conforming to IEC 60947-5-1 associated fuse rating
- 2.5 mOhm at 50 Hz - Ith 25 A power circuit average impedance
- 53.55 to 72.45 ms closing/16 to 24 ms opening operating time
- 3600 cycles/hr at <=140 deg F (60 deg C) operating rate
- With integral suppression device coil technology
- 5.4 W at 68 deg F (20 deg C) inrush power
- 5.4 W at 68 deg F (20 deg C) hold-in power consumption
- 28 ms time constant
- TH protective treatment
- 3 pollution deg
- -4 to 158 deg F permissible ambient air temperature around the device, -76 to 176 deg F storage temperature
- 9842.52 ft without derating in temperature operating altitude
- 1562 deg F (850 deg C) conforming to IEC 60695-2-1 fire resistance
- V1 conforming to UL 94 flame retardance
- Vibrations contactor open 2 gn, 5 to 300 Hz/vibrations contactor closed 4 gn, 5 to 300 Hz/shocks contactor closed 15 gn for 11 ms and shocks contactor open 6 gn for 11 ms mechanical robustness
- 25 to 400 Hz signaling circuit frequency
- 5 mA signaling circuit minimum switching current
 LC1D128BD StandardsUL 508|EN 60947-4-1|EN 60947-5-1|IEC 60947-4-1|IEC 60947-5-1|GOST|RINA|DNV|LROS|BV|CCC|GL|CSA C22.2 No 14SKU #2141805Part Number #LC1D128BDUNSPSC39121529UPC00785901787495