Part Number # DLMHBRAAA
SKU # 2444622
DLMHBRAAA
Ssac-Symcom DLMHBRAAA
Part Number # DLMHBRAAA
SKU # 2444622
Littelfuse DLMHBRAAA Key Features
| Brand: | Littelfuse |
|---|---|
| Part Number # : | DLMHBRAAA |
| SKU #: | 2444622 |
| Contact Configuration: | 1 Form C SPDT, SPDT/NO (1 Form C) |
| Dimensions: | 4.33 in H x 2.95 in W x 1.97 in D |
| Frequency Rating: | 50/60 Hz |
| Series: | DLMU |
| Terminal Type: | Screw |
| Trip Delay: | 1 to 30 s |
| Type: | 3-Phase Form 3 Isolated Electro Mechanical |
| Country of origin: | MX |
| Mounting type: | DIN Rail/Surface |
| Manufacturer Name: | Littelfuse |
| UNSPSC: | 39122332 |
| UPC: | 00079458992106 |
Buy Now Pay Later
Get 30 days to pay with Net 30 Terms. Apply Now.
Ssac-Symcom DLMHBRAAA
Brand: Littelfuse
Part Number: DLMHBRAAA
Littelfuse® SSAC® Voltage Monitoring Relay, 3-Phase Form 3 Isolated Electro Mechanical, Series: DLMU, 200 to 480 VAC, 50/60 Hz Frequency, SPDT/NO (1 Form C) Contact Configuration, DIN Rail/Surface Mounting, Screw Terminal, 1 to 30 s Trip Delay, 4.33 in H x 2.95 in W x 1.97 in D Dimensions
Additional Description: LTFS-DLMHBRAAA 3 PHASE VOLTAGE MONITOR
Catalog Description: The DLMU Series is a universal voltage, 3-phase voltage monitor. It continuously measures the voltage of each of the three phases with microcontroller accuracy and compares the value to preset trip points. It separately senses phase reversal and loss; over, under and unbalanced voltages; and over or under frequency. Protection is assured during periods of large average voltage fluctuations or when regenerated voltages are present. The unit trips within 200ms when phase loss is detected. Adjustable time delays are included to prevent nuisance tripping and short cycling of sensitive equipment. The isolated, 10A, SPDT and 2A alarm output relay contacts trip when a phase voltage exceeds the trip limits for the trip delay. Nominal line voltage, voltage unbalance, and time delays are knob adjustable. The phase loss setpoint and the acceptable frequency range are fixed. Both delta and wye systems can be monitored; no connection to neutral is required. See datasheet for operation details.
DLMHBRAAA Item Features
- Proprietary microcontroller based circuitry, constant monitoring to protect against phase loss, phase reversal, over voltage, under voltage, unbalance, short cycling and over/under frequency
- Universal line voltage range, flexibility to work in 200 to 480 VAC or 500 to 600 VAC applications
- DIN rail (35 mm) or surface mounting, installation flexibility
- LED indication provides diagnostics of relay, fault and time delay status
- User adjustable time delays prevents nuisance tripping and short cycling of sensitive equipment
- Staggered restart on restore
DLMHBRAAA Standards
UL Listed|CE Certified|cULus Listed|ASME A17.1 Rule 210.6|NEMA MG1 14:30, 14:35|IEEE C62.41SKU #2444622Part Number #DLMHBRAAAUNSPSC39122332UPC00079458992106
Image provided may only be a representation of final product and may include optional equipment