Square D GB2CB16 Tesys Gb2 Motor Circuit Protector
Image Disclaimers Message
Square D GB2CB16 Tesys Gb2 Motor Circuit Protector
Square D GB2CB16 Tesys Gb2 Motor Circuit Protector
Part #:GB2CB16
SKU #: 969308
Key Features
Part #:GB2CB16
SKU #: 969308
Brand: Square D
Actuator Type: Toggle
Amperage Rating: 10, 10 A
Dimensions: 15 mm W x 67 mm D x 74 mm H
Enclosure Type: IP20
Frequency Rating: 50/60, 50/60 Hz
- Category a conforming to IEC 60947-2, DC-12 conforming to IEC 60947-5-1, DC-13 conforming to IEC 60947-5-1 utilization category
- 50/60 Hz conforming to IEC 60947-2 network frequency
- 50% at 110 vac 50/60 Hz, 25% at 230/240 vac 50/60 Hz conforming to IEC 60947-2
- By clips mounting
- Horizontal/vertical mounting position
- Toggle control type
- 277 vac 50/60 Hz conforming to CSA C22.2 no 14, 48 VDC, 250 vac 50/60 Hz conforming to IEC 60947-2, 277 vac 50/60 Hz conforming to UL 1077 rated operational voltage
- 4 kV conforming to IEC 60947-2 rated impulse withstand voltage
- 2 W power dissipation per pole
- 8000 cycles mechanical durability
- 8000 cycles electrical durability
- Connector 1 cable 3/4 to 6 sq-mm, 3/4 to 4 sq-mm, 3/4 to 4 sq-mm, 3/4 to 2-1/2 sq-mm cable stiffness solid without cable end
- 1.2 N-m on connector tightening torque
- Shocks 22 gn for 20 ms conforming to IEC 60068-2-27, vibrations 5 Gn, 5 to 110 Hz conforming to IEC 60068-2-6 mechanical robustness
- (2) 9 mm pitches
- TC protective treatment
- IP20 conforming to IEC 60529 deg of protection
- -40 to 80 deg c ambient air temperature for storage
- 960 deg c conforming to IEC 60695-2-1 fire-resistance
- Icu = 50 kA at 230/240 VAC at 50/60 Hz, Icu = 1 kA at 48 VDC, Icu = 50 kA at 110 VAC 50/60 Hz, Icu = 1.5 kA at 24 VDC conforming to IEC 60947-2
Square D GB2CB16 Tesys Gb2 Motor Circuit Protector
Square D TeSys GB2 Motor Circuit Protector, Series: GB2, 250/277 VAC, 48 VDC, 10 A, 2 W Power, 50/60 Hz Frequency, 1 kA Interrupt, Thermal/Magnetic Trip, 138 A Trip, 1 Pole, Toggle Actuator, Cable Connection, 16 to 12 AWG Wire, IP20 Enclosure, DIN Rail/Plate Mounting, -20 to 60 deg C, 15 mm W x 67 mm D x 74 mm H Dimensions
Additional Description: SQD -GB2CB16 CONTROL CIRCUIT BREAKER
Catalog Description: TeSys GB2 thermal magnetic circuit protector, 1 P, 10 A, Id = 138 A